Mezzanine and Storage Platform Rules 2027 in Singapore
A single level storage platform in an industrial building needs no BCA plan approval only if it passes every limit in the Building Control Regulations 2003: storage use only, no public access, not more than 4 m high or 50 sqm, no beam or slab span over 6 m and no cantilever over 3 m. Any mezzanine that fails one of these tests is building works needing structural plans, a permit and a Qualified Person, and SCDF, URA and landlord rules apply either way.
Written in November 2026 from published rules; check the linked official sources for updates.
The pass-or-fail test for a storage platform
Answer each question for your platform. A single "no" means the BCA exemption does not apply. Each entry gives the test, who it applies to, the rule and where to read more.
Is it used solely for the storage of goods? Who: tenants and owners of industrial units. Rule: item (za) of the First Schedule covers storage only. A platform used as an office or work area is not covered. Read warehouse racking and storage platforms.
Is it in an industrial building or part of one? Who: industrial premises only. Rule: the exemption is limited to industrial buildings. Read insignificant building works.
Is it closed to the public? Who: all. Rule: the platform must not be accessible to the public.
Is it a single level? Who: all. Rule: the exemption covers a single level platform, including the space below it. A second level is building works.
Is it not more than 4 m high and 50 sqm in area? Who: all. Rule: both limits apply.
Is every beam or slab span not more than 6 m? Who: all. Rule: no span of a beam or slab that is part of the platform may exceed 6 m.
Is every cantilever not more than 3 m? Who: all. Rule: no cantilever that is part of the platform may exceed 3 m.
Is the staircase or ladder only for access to the platform? Who: all. Rule: item (zb) exempts the staircase, ladder or similar device used solely for access to such a platform.
Has the structure been designed for its load, including the floor below? Who: all. Rule: the exemption removes the BCA submission and nothing else. The platform and the slab beneath it still need to carry the load. Read machine foundations and floor loading.
Passing all nine means no BCA plan approval or permit. It does not remove the SCDF, URA and landlord points below.
If the platform fails the test
BCA: building works need approved structural plans and a permit before construction. Only a Qualified Person who is a PE in the civil or structural discipline can apply for structural plan approval, and the permit is applied for jointly by the developer, the Qualified Person and the builder. Structural plans without an Accredited Checker's certificate are processed within 7 working days of a complete submission. Read QP submission step by step.
SCDF: fire safety works need SCDF approval before they begin, with plans prepared and submitted by a Qualified Person. An FSC must be obtained before the premises are used or occupied. Read fire safety jargon explained.
URA: all covered floor area counts as GFA unless specifically exempted. A racking system is excluded from GFA only when it is standalone, modular, not an integral part of the building, used for storage related to the main industrial use, and accessed by people only for storing and retrieving goods.
JTC or landlord: on JTC land and buildings, JTC consent is required for additions and alterations even where other authorities approve. Read JTC factory renovation consent.
Storage limits under the Fire Code 2023
In a factory unit without sprinklers, storage areas including transient storage are limited to 100 sqm in aggregate (clause 9.6.1c). With an automatic sprinkler system the limit can be increased to 700 sqm. Beyond the limit, the whole unit must comply with the general warehouse requirements, or the storage must be compartmented from the factory. In a warehouse, clause 9.8 adds compartment size and storage height limits in Table 9.8A and requires maximum storage height to be marked on the walls with a red line and the words "No Storage Above This Line" at intervals of not more than 15 m. SCDF treats the use of factory space as storage as a change of use. Read factory change of use.
What MOM expects of racks in use
MOM's circular of 7 May 2015 on the safe use of storage racks asks that racks be structurally stable and designed for the intended use, that the safe working load be prominently displayed, that the design be re-assessed before any change of use including a change in the goods stored, and that racks, accessories and pallets be inspected regularly.
What has not changed
A permit is still required for all building works except insignificant building works.
The 4 m, 50 sqm, 6 m and 3 m limits are those in the First Schedule as published at November 2026.
Building works without approved plans or a permit carry a fine of up to $200,000, imprisonment of up to 2 years, or both.
CORENET X is mandatory for new projects of 5,000 sqm GFA and above from 1 October 2026. A platform within an existing unit is unlikely to be a new project of that size, but check your own submission route.
The Singapore Building Compliance Handbook 2027 places this topic alongside the others.
Common mistakes
A vendor installs a platform as if it were furniture. On 28 January 2025 a mezzanine floor and racking collapsed in a warehouse at 11 Toa Payoh Industrial Park, trapping three people. SCDF found no Fire Safety Certificate for the mezzanine and BCA had received no application. See unauthorised mezzanines and building works.
Assuming a platform over 50 sqm, with a second level, or used as a work area is exempt.
Re-using racks for heavier goods without re-assessment.
Treating landlord consent as authority approval.
Leaving an existing platform unapproved. See regularisation of unauthorised works.
FAQ
Does a storage platform need BCA approval?
Not if it passes every First Schedule limit above. Otherwise it needs plan approval and a permit.
Can an office be built on a mezzanine in a factory?
An office use is not storage, so the exemption does not apply. URA's use quantum rules also limit ancillary offices, as explained in factory change of use.
How much storage can a factory unit have?
Under the Fire Code 2023, 100 sqm without sprinklers or up to 700 sqm with an automatic sprinkler system, unless the unit meets warehouse requirements or the storage is compartmented.
Can an existing unapproved mezzanine be kept?
A Qualified Person can submit plans for approval, which is not guaranteed, and fire safety and planning requirements must also be met.
How are fees worked out?
See PE endorsement cost in Singapore. These are indicative points for context, not a benchmark or a quotation. Every project is different, so ask for a written quotation based on your drawings and scope.